APS-10K48SW-LCD
Provide Pure Sine Wave power for all your alternative energy needs with the MAGNIZON APS-10K48SW-LCD. This inverter/charger supplies 10000 watts of continuous 230V /50Hz AC power. Reliable large transformer design and frequency control powers very much compatible to all varieties of loads: resistive loads such as refrigerators, motors, pumps compressors and laser printers as well as electronic loads like TV’s, Computers, power tool and battery chargers. Smart micro controller based 3-stage charging system properly charge and maintain battery bank. The charge rate is selectable so you can use a variety of battery sizes and types to fit your back up time requirements.
Provides safe and reliable power protect for the following equipment:
| Input Phase & Wave Form | Single Phase & Sine wave (Utility or Generator) |
| Nominal Voltage | 220/230/240V AC |
| Input AC voltage Window | 154-273C AC |
| Line Low Transfer | 154V +/- 4% |
| Low Voltage Re engage | 164V +/- 4% |
| High Voltage Trip | 273V +/- 4% |
| High Voltage Re engage | 263V +/- 4% |
| Max Input AC Voltage | 270V |
| Nominal Input Frequency | 50Hz or 60Hz (Auto detect) |
| Low frequency trip | 40Hz |
| High frequency trip | 80Hz |
| Output Connection type | Hardwire via built in junction box with cover plate |
| Output Wave form & Phase | Pure Sine wave & Single Phase (Bypass mode sync to Input) |
| Power Factor | 1 |
| Nominal Output Voltage RMS | 220/230/240V AC (L-N) (same as input on Bypass mode) |
| Output Voltage regulation | +/-10% RMS (bypass mode sync to input) |
| Output frequency | 50Hz +/-0.3Hz or 60Hz+/-0.3Hz |
| Nominal Efficiency | >88% |
| Output Connection type | Hardwire via built in junction box with cover plate |
| Surge rating/crest factor | 3 times of rating |
| Output continuous power in Watts | 10000 |
| Output continuous power in VA | 10000 |
| Short circuit protection | Yes, fault after 10sec |
| Nominal Input Voltage Dc | 48V DC |
| Minimum start voltage Dc | 40V DC |
| Low battery Alarm | 44V DC |
| Low battery trip | 40V DC |
| High Voltage alarm | 64V DC |
| Over Charge Voltage | 62.8V DC |
| Max Charging Current | 85A DC |
| DC Connection type | DC INPUT: Set of 2 DC bolt-down terminals. AC INPUT: Hardwire via built in junction box with cover plate |
| Transfer Time | 6-10mSec |
| Line Mode | >95% |
| Battery Model | >85% |
| Power Save | Available when the load is less than 75W |
| 4-LED Status Display | Charge, Line, Inverter & fault |
| LCD Display | Input Voltage, Output Voltage, Frequency, Battery voltage, Load, Temperature, Charge current & Fault |
| Switch Selector | Saving Mode is On/Off when push the switch forward/backwards, keeping it horizontal is turning the inverter Off |
| Audible Alarm | Sounding when the heat sink's temperature is over 105deg C and shutdown after 30 seconds |
| Protections | Low Battery, Over charging, Over temp & over load |
| Communications | RJ11/RS232 (optional) |
| Operating Temp | 0-40deg C |
| Humidity | 0-95% RH (non-condensing) |
| Audible Noise | <60dB |
| Size (in mm) | 584x450x202 |
| Weight | 64Kgs |
| Warranty | 2 Year limited warranty Extendable up to 4 years |
| Safety | EMC/CE/ROHS/ISO9001 |
| Disturbance at Mains Terminals | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
| Radiated Disturbance | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
| Harmonic Current Emission | EN61000-3-12: 2011 |
| Voltage fluctuations & flickering | EN61000-3-11: 2000 |
| Electrostatic Discharge (ESD) | IEC 6100-4-2:2008 |
| Radio-frequency & continues radiated disturbances | IEC 6100-4-3:2006 + A1:2007 + A2:2010 |
| EFT/B Immunity | IEC 6100-4-4:2012 |
| Surge immunity | IEC 6100-4-5:2014 |
| Conducted RF immunity | IEC 6100-4-6:2013 |
| Power frequency magnetic field | IEC 6100-4-8:2009 |
| Voltage DIP | >95% reduction,IEC 6100-4-11:2004 |
| Voltage DIP | >30% reduction,IEC 6100-4-11:2004 |
| Voltage Interruption | IEC 6100-4-11:2004 |