APS-8048SW-LCD
Provide Pure Sine Wave power for all your alternative energy needs with the MAGNIZON APS-8048SW-LCD. This inverter/charger supplies 8000 watts of continuous 230V /50Hz AC power. Reliable large transformer design and frequency control powers very much compatible to all varieties of loads: resistive loads such as refrigerators, motors, pumps compressors and laser printers as well as electronic loads like TV’s, Computers, power tool and battery chargers. Smart micro controller based 3-stage charging system properly charge and maintain battery bank. The charge rate is selectable so you can use a variety of battery sizes and types to fit your back up time requirements.
Provides safe and reliable power protect for the following equipment:
On inverter
On battery charger
On Transfer
On remote control & other features
**Built in input and output breakers.
Input Phase & Wave Form | Single Phase & Sine wave (Utility or Generator) |
Nominal Voltage | 220/230/240V AC |
Input AC voltage Window | 154-273C AC |
Line Low Transfer | 154V +/- 4% |
Low Voltage Re engage | 164V +/- 4% |
High Voltage Trip | 273V +/- 4% |
High Voltage Re engage | 263V +/- 4% |
Max Input AC Voltage | 270V |
Nominal Input Frequency | 50Hz or 60Hz (Auto detect) |
Low frequency trip | 40Hz |
High frequency trip | 80Hz |
Output Connection type | Hardwire via built in junction box with cover plate |
Output Wave form & Phase | Pure Sine wave & Single Phase (Bypass mode sync to Input) |
Power Factor | 1 |
Nominal Output Voltage RMS | 220/230/240V AC (L-N) (same as input on Bypass mode) |
Output Voltage regulation | +/-10% RMS (bypass mode sync to input) |
Output frequency | 50Hz +/-0.3Hz or 60Hz+/-0.3Hz |
Nominal Efficiency | >88% |
Output Connection type | Hardwire via built in junction box with cover plate |
Surge rating/crest factor | 3 times of rating |
Output continuous power in Watts | 8000 |
Output continuous power in VA | 8000 |
Short circuit protection | Yes, fault after 10sec |
Nominal Input Voltage Dc | 48V DC |
Minimum start voltage Dc | 40V DC |
Low battery Alarm | 44V DC |
Low battery trip | 40V DC |
High Voltage alarm | 64V DC |
Over Charge Voltage | 62.8V DC |
Max Charging Current | 75A DC |
DC Connection type | DC INPUT: Set of 2 DC bolt-down terminals. AC INPUT: Hardwire via built in junction box with cover plate |
Transfer Time | 6-10mSec |
Line Mode | >95% |
Battery Model | >85% |
Power Save | Available when the load is less than 75W |
4-LED Status Display | Charge, Line, Inverter & fault |
LCD Display | Input Voltage, Output Voltage, Frequency, Battery voltage, Load, Temperature, Charge current & Fault |
Switch Selector | Saving Mode is On/Off when push the switch forward/backwards, keeping it horizontal is turning the inverter Off |
Audible Alarm | Sounding when the heat sink's temperature is over 105deg C and shutdown after 30 seconds |
Protections | Low Battery, Over charging, Over temp & over load |
Communications | RJ11/RS232 (optional) |
Operating Temp | 0-40deg C |
Humidity | 0-95% RH (non-condensing) |
Audible Noise | <60dB |
Size (in mm) | 549x450x202 |
Weight | 56Kgs |
Warranty | 2 Year limited warranty Extendable up to 4 years |
Safety | EMC/CE/ROHS/ISO9001 |
Disturbance at Mains Terminals | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
Radiated Disturbance | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
Harmonic Current Emission | EN61000-3-12: 2011 |
Voltage fluctuations & flickering | EN61000-3-11: 2000 |
Electrostatic Discharge (ESD) | IEC 6100-4-2:2008 |
Radio-frequency & continues radiated disturbances | IEC 6100-4-3:2006 + A1:2007 + A2:2010 |
EFT/B Immunity | IEC 6100-4-4:2012 |
Surge immunity | IEC 6100-4-5:2014 |
Conducted RF immunity | IEC 6100-4-6:2013 |
Power frequency magnetic field | IEC 6100-4-8:2009 |
Voltage DIP | >95% reduction,IEC 6100-4-11:2004 |
Voltage DIP | >30% reduction,IEC 6100-4-11:2004 |
Voltage Interruption | IEC 6100-4-11:2004 |