APS-4024SW-LCD
Provide Pure Sine Wave power for all your alternative energy needs with the Magnizon APS-4024SW-LCD. This inverter/charger supplies 4000 watts of continuous 230V /50Hz AC power. Reliable large pure copper based transformer design and frequency controlled power, very much compatible to all varieties of loads: resistive loads such as refrigerators, motors, pumps, compressors and laser printers as well as electronic loads like TV’s, Computers, power tool and battery chargers. Smart micro controller based 3-stage charging system properly charge and maintain battery bank. The charge rate is selectable so you can use a variety of battery sizes and types to fit your back up time requirements.
| Input Wave Form | Sine wave (Utility or Generator) |
| Nominal Voltage | 230V AC |
| Low Voltage Trip | 154V +/- 4% |
| Low Voltage Re engage | 164V +/- 4% |
| High Voltage Trip | 253V +/- 4% |
| High Voltage Re engage | 243V +/- 4% |
| Max Input AC Voltage | 270V |
| Nominal Input Frequency | 50Hz or 60Hz (Auto detect) |
| Low frequency trip | 47Hz for 50Hz, 57Hz for 60Hz |
| High frequency trip | 55Hz for 50Hz, 65Hz for 60Hz |
| Output Wave form(bypass mode) | Same as Input |
| Overload protection | Circuit breaker |
| Short circuit protection | Circuit breaker |
| Efficiency on line transfer mode | 0.95 |
| Line transfer time | 10 mSec Typical |
| Bypass without Battery connected | Yes |
| Max bypass current | 40Amp |
| Output Wave form | Pure Sine wave |
| Output continuous power in Watts | 4000 |
| Output continuous power in VA | 4000 |
| Power Factor | 1 |
| Nominal Output Voltage RMS | 230V AC (L-N) |
| Output Voltage regulation | +/-10% rms |
| Output frequency | 50Hz +/-0.3Hz or 60Hz+/-0.3Hz |
| Nominal Efficiency | >88% |
| Surge rating | 9000 |
| Short circuit protection | Yes, fault after 10sec |
| Nominal Input Voltage Dc | 24V |
| Minimum start voltage Dc | 20V |
| Low battery Alarm | 21V |
| Low battery trip | 20V |
| High Voltage alarm | 32V |
| Power Saver | Below 25Watts when enabled |
| Power Saver | Same switched On/Off remote |
| Input connection type | Terminal block with secure enclosure |
| AC input Voltage Range | 164-253V AC |
| Output Voltage (DC) | Depends on battery type |
| Battery Charge current | 65Amp |
| Battery initial Voltage for start up | 0-31.4V DC |
| Over charge protection shutdown | 31.4V DC |
| Gel USA (Boost Voltage) | 14.00 |
| AGM.1 (Boost Voltage) | 14.10 |
| AGM.2 (Boost Voltage) | 14.60 |
| Sealed Lead acid (Boost Voltage) | 14.40 |
| Gel Euro (Boost Voltage) | 14.40 |
| Open Lead acid (Boost Voltage) | 14.80 |
| Calcium (Boost Voltage) | 15.10 |
| Gel USA (Float Voltage) | 13.70 |
| AGM.1 (Float Voltage) | 13.40 |
| AGM.2 (Float Voltage) | 13.70 |
| Sealed Lead acid (Float Voltage) | 13.60 |
| Gel Euro (Float Voltage) | 13.80 |
| Open Lead acid (Float Voltage) | 13.30 |
| Calcium (Float Voltage) | 13.60 |
| De-sulphation | 15.5 for 4hrs |
| Remote control/RS232/USB | Yes. Optional |
| Size (in mm) | 598x218x119 |
| Weight | 35kgs |
| Warranty | 2 Year limited warranty Extendable up to 4 years |
| Safety | EMC/CE/ROHS/ISO9001/ISO14001 |
| Disturbance at Mains Terminals | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
| Radiated Disturbance | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
| Harmonic Current Emission | EN61000-3-12: 2011 |
| Voltage fluctuations & flickering | EN61000-3-11: 2000 |
| Electrostatic Discharge (ESD) | IEC 6100-4-2:2008 |
| Radio-frequency & continuous radiated disturbances | IEC 6100-4-3:2006 + A1:2007 + A2:2010 |
| EFT/B Immunity | IEC 6100-4-4:2012 |
| Surge immunity | IEC 6100-4-5:2014 |
| Conducted RF immunity | IEC 6100-4-6:2013 |
| Power frequency magnetic field | IEC 6100-4-8:2009 |
| Voltage DIP | >95% reduction,IEC 6100-4-11:2004 |
| Voltage DIP | >30% reduction,IEC 6100-4-11:2004 |
| Voltage Interruption | IEC 6100-4-11:2004 |