APS-1012SW-LCD
Magnizon Pure Sine Wave inverter APS-1012SW-LCD provide power for all your alternative energy needs . This inverter/charger supplies 1000 watts of continuous 230V /50Hz AC power. Reliable large pure copper based transformer design and frequency controlled power, very much compatible to all varieties of loads: resistive loads such as refrigerators, motors, pumps, compressors and laser printers as well as electronic loads like TV’s, Computers, power tool and battery chargers. Smart micro controller based 3-stage charging system properly charge and maintain battery bank. The charge rate is selectable so you can use a variety of battery sizes and types to fit your back up time requirements
Input Wave Form | Sine wave (Utility or Generator) |
Nominal Voltage | 230V AC |
Low Voltage Trip | 154V +/- 4% |
Low Voltage Re engage | 164V +/- 4% |
High Voltage Trip | 253V +/- 4% |
High Voltage Re engage | 243V +/- 4% |
Max Input AC Voltage | 270V |
Nominal Input Frequency | 50Hz or 60Hz (Auto detect) |
Low frequency trip | 47Hz for 50Hz, 57Hz for 60Hz |
High frequency trip | 55Hz for 50Hz, 65Hz for 60Hz |
Output Wave form(bypass mode) | Same as Input |
Overload protection | Circuit breaker |
Short circuit protection | Circuit breaker |
Efficiency on line transfer mode | 0.95 |
Line transfer time | 10 mSec Typical |
Bypass without Battery connected | Yes |
Max bypass current | 40Amp |
Output Wave form | Pure Sine wave |
Output continuous power in Watts | 1000 |
Output continuous power in VA | 1000 |
Power Factor | 1 |
Nominal Output Voltage RMS | 230V AC (L-N) |
Output Voltage regulation | +/-10% rms |
Output frequency | 50Hz +/-0.3Hz or 60Hz+/-0.3Hz |
Nominal Efficiency | >88% |
Surge rating | 3000 |
Short circuit protection | Yes, fault after 10sec |
Nominal Input Voltage Dc | 12V |
Minimum start voltage Dc | 10V |
Low battery Alarm | 10.5V |
Low battery trip | 10V |
High Voltage alarm | 16V |
Power Saver | Below 25Watts when enabled |
Power Saver | Same switched On/Off remote |
Input connection type | Terminal block with secure enclosure |
AC input Voltage Range | 164-253V AC |
Output Voltage (DC) | Depends on battery type |
Battery Charge current | 35Amp |
Battery initial Voltage for start up | 0-15.7V DC |
Over charge protection shutdown | 15.7V DC |
Gel USA Boost Voltage (Per battery) | 14 |
AGM.1 Boost Voltage (Per battery) | 14.1 |
AGM.2 Boost Voltage (Per battery) | 14.6 |
Sealed Lead acid Boost Voltage (Per battery) | 14.4 |
Gel Euro Boost Voltage (Per battery) | 14.4 |
Open Lead acid Boost Voltage (Per battery) | 14.8 |
Calcium Boost Voltage (Per battery) | 15.1 |
Gel USA Float Voltage (Per Battery) | 13.7 |
AGM.1 Float Voltage (Per Battery) | 13.4 |
AGM.2 Float Voltage (Per Battery) | 13.7 |
Sealed Lead acid Float Voltage (Per Battery) | 13.6 |
Gel Euro Float Voltage (Per Battery) | 13.8 |
Open Lead acid Float Voltage (Per Battery) | 13.3 |
Calcium Float Voltage (Per Battery) | 13.6 |
De-sulphation | 15.5 for 4hrs |
Remote control/RS232/USB | Yes. Optional |
Size (in mm) | 442x218x179 |
Weight | 14kgs |
Warranty | 2 Year limited warranty Extendable up to 4 years |
Safety | EMC/CE/ROHS/ISO9001 |
Disturbance at Mains Terminals | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
Radiated Disturbance | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
Harmonic Current Emission | EN61000-3-12: 2011 |
Voltage fluctuations & flickering | EN61000-3-11: 2000 |
Electrostatic Discharge (ESD) | IEC 6100-4-2:2008 |
Radio-frequency & continuous radiated disturbances | IEC 6100-4-3:2006 + A1:2007 + A2:2010 |
EFT/B Immunity | IEC 6100-4-4:2012 |
Surge immunity | IEC 6100-4-5:2014 |
Conducted RF immunity | IEC 6100-4-6:2013 |
Power frequency magnetic field | IEC 6100-4-8:2009 |
Voltage DIP | >95% reduction,IEC 6100-4-11:2004 |
Voltage DIP | >30% reduction,IEC 6100-4-11:2004 |
Voltage Interruption | IEC 6100-4-11:2004 |